Calculates, for each
cell, the least accumulative cost distance from or to the least-cost source,
while accounting for surface distance along with horizontal and vertical cost
factors.
1.Input raster or feature source data
The input source
locations.
This is a raster or
feature dataset that identifies the cells or locations from or to which the
least accumulated cost distance for every output cell location is calculated.
For rasters, the input
type can be integer or floating point.
2.Output distance raster
The output path distance
raster.
The output path distance
raster identifies, for each cell, the least accumulative cost distance, over a
cost surface to the identified source locations, while accounting for surface
distance as well as horizontal and vertical surface factors.
A source can be a cell,
a set of cells, or one or more feature locations.
The output raster is of
floating-point type.
3.Input cost raster (optional)
A raster defining the impedance
or cost to move planimetrically through each cell.
The value at each cell
location represents the cost-per-unit distance for moving through the cell.
Each cell location value is multiplied by the cell resolution while also
compensating for diagonal movement to obtain the total cost of passing through
the cell.
The values of the cost
raster can be integer or floating point, but they cannot be negative or zero
(you cannot have a negative or zero cost).
4.Input surface raster (optional)
A raster defining the elevation
values at each cell location.
The values are used to
calculate the actual surface distance covered when passing between cells.
5.Maximum distance (optional)
The threshold that the
accumulative cost values cannot exceed.
If an accumulative cost
distance value exceeds this value, the output value for the cell location will
be NoData. The maximum distance is the extent for which the accumulative cost
distances are calculated.
The default distance is
to the edge of the output raster.
6.Output backlink raster (optional)
The output cost backlink
raster.
The backlink raster
contains values 0 through 8, which define the direction or identify the next
neighboring cell (the succeeding cell) along the least accumulative cost path
from a cell to reach its least-cost source, while accounting for surface
distance as well as horizontal and vertical surface factors.
If the path is to pass
into the right neighbor, the cell will be assigned the value 1, 2 for the lower
right diagonal cell, and continue clockwise. The value 0 is reserved for source
cells.
7.Input horizontal raster (optional)
A raster defining the
horizontal direction at each cell.
The values on the raster
must be integers ranging from 0 to 360, with 0 degrees being north, or toward
the top of the screen, and increasing clockwise. Flat areas should be given a
value of -1. The values at each location will be used in conjunction with the
Horizontal factor to determine the horizontal cost incurred when moving from a
cell to its neighbors.
8.Horizontal factor (optional)
Specifies the
relationship between the horizontal cost factor and the horizontal relative
moving angle (HRMA).
There are several
factors with modifiers from which to select that identify a defined horizontal
factor graph. Additionally, a table can be used to create a custom graph. The
graphs are used to identify the horizontal factor used in calculating the total
cost for moving into a neighboring cell.
In the descriptions
below, two acronyms are used: HF stands for horizontal factor, which defines
the horizontal difficulty encountered when moving from one cell to the next;
and HRMA stands for horizontal relative moving angle, which identifies the
angle between the horizontal direction from a cell and the moving direction.
The Horizontal factor
options are as follows:
Binary—If the HRMA is less than the cut angle, the HF is set to
the value associated with the zero factor; otherwise, it is infinity.
Forward—Only forward movement is allowed. The HRMA must be greater
than or equal to 0 and less than 90 degrees (0 <= HRMA < 90). If the HRMA
is greater than 0 and less than 45 degrees, the HF for the cell is set to the
value associated with the zero factor. If the HRMA is greater than or equal to
45 degrees, the side value modifier value is used. The HF for any HRMA equal to
or greater than 90 degrees is set to infinity.
Linear—The HF is a linear function of the HRMA.
Inverse Linear—The HF is an inverse linear function of the HRMA.
Table—A table file will be used to define the horizontal factor
graph used to determine the HFs.
Modifiers to the
horizontal factors are the following:
Zerofactor—The horizontal factor to be used when the HRMA is zero. This factor positions the y-intercept for any of the horizontal factor functions.
Cut angle—The HRMA angle beyond which the HF will be set to infinity.
Slope—The slope of the straight line used with the Linear and Inverse Linear horizontal factor keywords. The slope is specified as a fraction of rise over run (for example,45 percent slope is 1/45, which is input as 0.02222).
Side value—The HF when the HRMA is greater than or equal to 45 degrees and less than 90 degrees when the Forward horizontal factor keyword is specified.
Table name—The name of the table defining the HF.
9.Multiplier to apply to costs (optional)
The multiplier to apply
to the cost values.
This allows for control
of the mode of travel or the magnitude at a source. The greater the multiplier,
the greater the cost to move through each cell.
The values must be
greater than zero. The default is 1.
10.Start cost (optional)
The starting cost from
which to begin the cost calculations.
Allows for the
specification of the fixed cost associated with a source. Instead of starting
at a cost of zero, the cost algorithm will begin with the value set by Start
cost.
The values must be zero
or greater. The default is 0.
11.Accumulative cost resistance rate (optional)
This parameter simulates
the increase in the effort to overcome costs as the accumulative cost
increases. It is used to model fatigue of the traveler. The growing
accumulative cost to reach a cell is multiplied by the resistance rate and
added to the cost to move into the subsequent cell.
It is a modified version
of a compound interest rate formula that is used to calculate the apparent cost
of moving through a cell. As the value of the resistance rate increases, it
increases the cost of the cells that are visited later. The greater the
resistance rate, the more additional cost is added to reach the next cell,
which is compounded for each subsequent movement. Since the resistance rate is similar
to a compound rate and generally the accumulative cost values are very large,
small resistance rates are suggested, such as 0.02, 0.005, or even smaller,
depending on the accumulative cost values.
The values must be zero
or greater. The default is 0.
12.Capacity (optional)
The cost capacity for
the traveler for a source.
The cost calculations
continue for each source until the specified capacity is reached.
The values must be
greater than zero. The default capacity is to the edge of the output raster.
13.Travel direction (optional)
Specifies the direction
of the traveler when applying horizontal and vertical factors, the source
resistance rate, and the source starting cost.
FROM_SOURCE—The horizontal factor, vertical factor, source
resistance rate, and source starting cost will be applied beginning at the
input source, and travel out to the nonsource cells. This is the default.
TO_SOURCE—The horizontal factor, vertical factor, source
resistance rate, and source starting cost will be applied beginning at each
nonsource cell and travel back to the input source.
If you select the String
option, you can choose between from and to options, which will be applied to all
sources.
If you select the Field
option, you can select the field from the source data that determines the
direction to use for each source. The field must contain the text string
FROM_SOURCE or TO_SOURCE.
Path
Distance Back Link
How to use Path Distance
Back LinkTool in Arc Toolbox ArcMap ArcGIS??
Path Distance Back Link
Path
to access the tool
:
Path
Distance Back LinkTool, Distance Toolset, Spatial
Analyst Tools Toolbox
Path Distance Back Link
Defines the neighbor
that is the next cell on the least accumulative cost path to the least-cost
source, while accounting for surface distance along with horizontal and
vertical cost factors.
1. Input raster or feature source data
The input source
locations.
This is a raster or
feature dataset that identifies the cells or locations from or to which the
least accumulated cost distance for every output cell location is calculated.
For rasters, the input
type can be integer or floating point.
2.Output backlink raster
The output cost backlink
raster.
The backlink raster
contains values 0 through 8, which define the direction or identify the next
neighboring cell (the succeeding cell) along the least accumulative cost path
from a cell to reach its least-cost source, while accounting for surface
distance as well as horizontal and vertical surface factors.
If the path is to pass
into the right neighbor, the cell will be assigned the value 1, 2 for the lower
right diagonal cell, and continue clockwise. The value 0 is reserved for source
cells.
3.Input cost raster (optional)
A raster defining the
impedance or cost to move planimetrically through each cell.
The value at each cell
location represents the cost-per-unit distance for moving through the cell.
Each cell location value is multiplied by the cell resolution while also
compensating for diagonal movement to obtain the total cost of passing through
the cell.
The values of the cost
raster can be integer or floating point, but they cannot be negative or zero
(you cannot have a negative or zero cost).
4.Input surface raster (optional)
A raster defining the
elevation values at each cell location.
The values are used to
calculate the actual surface distance covered when passing between cells.
5.Maximum distance (optional)
The threshold that the
accumulative cost values cannot exceed.
If an accumulative cost
distance value exceeds this value, the output value for the cell location will
be NoData. The maximum distance is the extent for which the accumulative cost
distances are calculated.
The default distance is
to the edge of the output raster.
6.Output distance raster (optional)
The output path distance
raster.
The output path distance
raster identifies, for each cell, the least accumulative cost distance, over a
cost surface to the identified source locations, while accounting for surface
distance as well as horizontal and vertical surface factors.
A source can be a cell,
a set of cells, or one or more feature locations.
The output raster is of
floating-point type.
7.Horizontal factor parameters (optional)
8.Vertical Factor parameters (optional)
9. Source Characteristics
A raster defining the horizontal direction at each cell.
The values on the raster must be integers ranging from 0 to 360, with 0
degrees being north, or toward the top of the screen, and increasing clockwise.
Flat areas should be given a value of -1. The values at each location will be
used in conjunction with the Horizontal factor to determine the horizontal cost
incurred when moving from a cell to its neighbors.
Horizontal
factor (optional)
Specifies the relationship between the horizontal cost factor and the
horizontal relative moving angle (HRMA).
There are several factors with modifiers from which to select that
identify a defined horizontal factor graph. Additionally, a table can be used
to create a custom graph. The graphs are used to identify the horizontal factor
used in calculating the total cost for moving into a neighboring cell.
In the descriptions below, two acronyms are used: HF stands for horizontal
factor, which defines the horizontal difficulty encountered when moving from
one cell to the next; and HRMA stands for horizontal relative moving angle,
which identifies the angle between the horizontal direction from a cell and the
moving direction.
The Horizontal factor options are as follows:
·Binary—If the HRMA is less than the cut angle, the HF is set to the value
associated with the zero factor; otherwise, it is infinity.
·Forward—Only forward movement is allowed. The HRMA must be greater than or
equal to 0 and less than 90 degrees (0 <= HRMA < 90). If the HRMA is
greater than 0 and less than 45 degrees, the HF for the cell is set to the
value associated with the zero factor. If the HRMA is greater than or equal to
45 degrees, the side value modifier value is used. The HF for any HRMA equal to
or greater than 90 degrees is set to infinity.
·Linear—The HF is a linear function of the HRMA.
·Inverse Linear—The HF is an inverse linear function of the HRMA.
·Table—A table file will be used to define the horizontal factor graph used
to determine the HFs.
Modifiers to the horizontal factors are the following:
·Zero factor—The horizontal factor to be used when the HRMA is zero. This
factor positions the y-intercept for any of the horizontal factor functions.
·Cut angle—The HRMA angle beyond which the HF will be set to infinity.
·Slope—The slope of the straight line used with the Linear and Inverse
Linear horizontal factor keywords. The slope is specified as a fraction of rise
over run (for example, 45 percent slope is 1/45, which is input as 0.02222).
·Side value—The HF when the HRMA is greater than or equal to 45 degrees and
less than 90 degrees when the Forward horizontal factor keyword is specified.
·Table name—The name of the table defining the HF.
Input
vertical raster (optional)
A raster defining the z-values for each cell location.
The values are used for calculating the slope used to identify the
vertical factor incurred when moving from one cell to another.
Vertical
factor (optional)
Specifies the relationship between the vertical cost factor and the
vertical relative moving angle (VRMA).
There are several factors with modifiers from which to select that
identify a defined vertical factor graph. Additionally, a table can be used to
create a custom graph. The graphs are used to identify the vertical factor used
in calculating the total cost for moving into a neighboring cell.
In the descriptions below, two acronyms are used: VF stands for vertical
factor, which defines the vertical difficulty encountered in moving from one
cell to the next; and VRMA stands for vertical relative moving angle, which
identifies the slope angle between the FROM or processing cell and the TO cell.
The Vertical factor options are as follows:
·Binary—If the VRMA is greater than the low-cut angle and less than the
high-cut angle, the VF is set to the value associated with the zero factor;
otherwise, it is infinity.
·Linear—The VF is a linear function of the VRMA.
·Symmetric Linear—The VF is a linear function of the VRMA in either the
negative or positive side of the VRMA, respectively, and the two linear
functions are symmetrical with respect to the VF (y) axis.
·Inverse Linear—The VF is an inverse linear function of the VRMA.
·Symmetric Inverse Linear—The VF is an inverse linear function of the VRMA
in either the negative or positive side of the VRMA, respectively, and the two
linear functions are symmetrical with respect to the VF (y) axis.
·Cos—The VF is the cosine-based function of the VRMA.
·Sec—The VF is the secant-based function of the VRMA.
·Cos-Sec—The VF is the cosine-based function of the VRMA when the VRMA is
negative and is the secant-based function of the VRMA when the VRMA is
nonnegative.
·Sec-Cos—The VF is the secant-based function of the VRMA when the VRMA is
negative and is the cosine-based function of the VRMA when the VRMA is
nonnegative.
·Table—A table file will be used to define the vertical-factor graph used
to determine the VFs.
Modifiers to the vertical keywords are the following:
·Zero factor—The vertical factor used when the VRMA is zero. This factor
positions the y-intercept of the specified function. By definition, the zero
factor is not applicable to any of the trigonometric vertical functions (COS,
SEC, COS-SEC, or SEC-COS). The y-intercept is defined by these functions.
·Low Cut angle—The VRMA angle below which the VF will be set to infinity.
·High Cut angle—The VRMA angle above which the VF will be set to infinity.
·Slope—The slope of the straight line used with the Linear and Inverse
Linear vertical-factor keywords. The slope is specified as a fraction of rise
over run (for example, 45 percent slope is 1/45, which is input as 0.02222).
·Table name—The name of the table defining the VF.
Multiplier
to apply to costs (optional)
The multiplier to apply to the cost values.
This allows for control of the mode of travel or the magnitude at a
source. The greater the multiplier, the greater the cost to move through each
cell.
The values must be greater than zero. The default is 1.
Start cost
(optional)
The starting cost from which to begin the cost calculations.
Allows for the specification of the fixed cost associated with a source.
Instead of starting at a cost of zero, the cost algorithm will begin with the
value set by Start cost.
The values must be zero or greater. The default is 0.
Accumulative
cost resistance rate (optional)
This parameter simulates the increase in the effort to overcome costs as
the accumulative cost increases. It is used to model fatigue of the traveler.
The growing accumulative cost to reach a cell is multiplied by the resistance
rate and added to the cost to move into the subsequent cell.
It is a modified version of a compound interest rate formula that is used
to calculate the apparent cost of moving through a cell. As the value of the
resistance rate increases, it increases the cost of the cells that are visited
later. The greater the resistance rate, the more additional cost is added to
reach the next cell, which is compounded for each subsequent movement. Since
the resistance rate is similar to a compound rate and generally the
accumulative cost values are very large, small resistance rates are suggested,
such as 0.02, 0.005, or even smaller, depending on the accumulative cost
values.
The values must be zero or greater. The default is 0.
Capacity
(optional)
The cost capacity for the traveler for a source.
The cost calculations continue for each source until the specified
capacity is reached.
The values must be greater than zero. The default capacity is to the edge
of the output raster.
Travel
direction (optional)
Specifies the direction of the traveler when applying horizontal and
vertical factors, the source resistance rate, and the source starting cost.
·FROM_SOURCE—The horizontal factor, vertical factor, source resistance
rate, and source starting cost will be applied beginning at the input source,
and travel out to the nonsource cells. This is the default.
·TO_SOURCE—The horizontal factor, vertical factor, source resistance rate,
and source starting cost will be applied beginning at each nonsource cell and
travel back to the input source.
If you select the String option, you can choose between from and to
options, which will be applied to all sources.
If you select the Field option, you can select the field from the source
data that determines the direction to use for each source. The field must
contain the text string FROM_SOURCE or TO_SOURCE.
Output
distance raster (optional)
The output path distance raster.
The output path distance raster identifies, for each cell, the least
accumulative cost distance, over a cost surface to the identified source
locations, while accounting for surface distance as well as horizontal and
vertical surface factors.
A source can be a cell, a set of cells, or one or more feature locations.
The output raster is of floating-point type.
Input
horizontal raster (optional)
A raster defining the horizontal direction at each cell.
The values on the raster must be integers ranging from 0 to 360, with 0
degrees being north, or toward the top of the screen, and increasing clockwise.
Flat areas should be given a value of -1. The values at each location will be
used in conjunction with the Horizontal factor to determine the horizontal cost
incurred when moving from a cell to its neighbors.
Horizontal
factor (optional)
Specifies the relationship between the horizontal cost factor and the
horizontal relative moving angle (HRMA).
There are several factors with modifiers from which to select that
identify a defined horizontal factor graph. Additionally, a table can be used
to create a custom graph. The graphs are used to identify the horizontal factor
used in calculating the total cost for moving into a neighboring cell.
In the descriptions below, two acronyms are used: HF stands for horizontal
factor, which defines the horizontal difficulty encountered when moving from
one cell to the next; and HRMA stands for horizontal relative moving angle,
which identifies the angle between the horizontal direction from a cell and the
moving direction.
The Horizontal factor options are as follows:
·Binary—If the HRMA is less than the cut angle, the HF is set to the value
associated with the zero factor; otherwise, it is infinity.
·Forward—Only forward movement is allowed. The HRMA must be greater than or
equal to 0 and less than 90 degrees (0 <= HRMA < 90). If the HRMA is
greater than 0 and less than 45 degrees, the HF for the cell is set to the
value associated with the zero factor. If the HRMA is greater than or equal to
45 degrees, the side value modifier value is used. The HF for any HRMA equal to
or greater than 90 degrees is set to infinity.
·Linear—The HF is a linear function of the HRMA.
·Inverse Linear—The HF is an inverse linear function of the HRMA.
·Table—A table file will be used to define the horizontal factor graph used
to determine the HFs.
Modifiers to the horizontal factors are the following:
·Zero factor—The horizontal factor to be used when the HRMA is zero. This
factor positions the y-intercept for any of the horizontal factor functions.
·Cut angle—The HRMA angle beyond which the HF will be set to infinity.
·Slope—The slope of the straight line used with the Linear and Inverse
Linear horizontal factor keywords. The slope is specified as a fraction of rise
over run (for example, 45 percent slope is 1/45, which is input as 0.02222).
·Side value—The HF when the HRMA is greater than or equal to 45 degrees and
less than 90 degrees when the Forward horizontal factor keyword is specified.
·Table name—The name of the table defining the HF.
Input
vertical raster (optional)
A raster defining the z-values for each cell location.
The values are used for calculating the slope used to identify the
vertical factor incurred when moving from one cell to another.
Vertical
factor (optional)
Specifies the relationship between the vertical cost factor and the
vertical relative moving angle (VRMA).
There are several factors with modifiers from which to select that
identify a defined vertical factor graph. Additionally, a table can be used to
create a custom graph. The graphs are used to identify the vertical factor used
in calculating the total cost for moving into a neighboring cell.
In the descriptions below, two acronyms are used: VF stands for vertical
factor, which defines the vertical difficulty encountered in moving from one
cell to the next; and VRMA stands for vertical relative moving angle, which
identifies the slope angle between the FROM or processing cell and the TO cell.
The Vertical factor options are as follows:
·Binary—If the VRMA is greater than the low-cut angle and less than the
high-cut angle, the VF is set to the value associated with the zero factor;
otherwise, it is infinity.
·Linear—The VF is a linear function of the VRMA.
·Symmetric Linear—The VF is a linear function of the VRMA in either the
negative or positive side of the VRMA, respectively, and the two linear
functions are symmetrical with respect to the VF (y) axis.
·Inverse Linear—The VF is an inverse linear function of the VRMA.
·Symmetric Inverse Linear—The VF is an inverse linear function of the VRMA
in either the negative or positive side of the VRMA, respectively, and the two
linear functions are symmetrical with respect to the VF (y) axis.
·Cos—The VF is the cosine-based function of the VRMA.
·Sec—The VF is the secant-based function of the VRMA.
·Cos-Sec—The VF is the cosine-based function of the VRMA when the VRMA is
negative and is the secant-based function of the VRMA when the VRMA is
nonnegative.
·Sec-Cos—The VF is the secant-based function of the VRMA when the VRMA is
negative and is the cosine-based function of the VRMA when the VRMA is
nonnegative.
·Table—A table file will be used to define the vertical-factor graph used
to determine the VFs.
Modifiers to the vertical keywords are the following:
·Zero factor—The vertical factor used when the VRMA is zero. This factor
positions the y-intercept of the specified function. By definition, the zero
factor is not applicable to any of the trigonometric vertical functions (COS,
SEC, COS-SEC, or SEC-COS). The y-intercept is defined by these functions.
·Low Cut angle—The VRMA angle below which the VF will be set to infinity.
·High Cut angle—The VRMA angle above which the VF will be set to infinity.
·Slope—The slope of the straight line used with the Linear and Inverse
Linear vertical-factor keywords. The slope is specified as a fraction of rise
over run (for example,
45 percent slope is 1/45, which is input as 0.02222).
·Table name—The name of the table defining the VF.
Multiplier
to apply to costs (optional)
The multiplier to apply to the cost values.
This allows for control of the mode of travel or the magnitude at a
source. The greater the multiplier, the greater the cost to move through each
cell.
The values must be greater than zero. The default is 1.
Start cost
(optional)
The starting cost from which to begin the cost calculations.
Allows for the specification of the fixed cost associated with a source.
Instead of starting at a cost of zero, the cost algorithm will begin with the
value set by Start cost.
The values must be zero or greater. The default is 0.
Accumulative
cost resistance rate (optional)
This parameter simulates the increase in the effort to overcome costs as
the accumulative cost increases. It is used to model fatigue of the traveler.
The growing accumulative cost to reach a cell is multiplied by the resistance
rate and added to the cost to move into the subsequent cell.
It is a modified version of a compound interest rate formula that is used
to calculate the apparent cost of moving through a cell. As the value of the
resistance rate increases, it increases the cost of the cells that are visited
later. The greater the resistance rate, the more additional cost is added to
reach the next cell, which is compounded for each subsequent movement. Since
the resistance rate is similar to a compound rate and generally the
accumulative cost values are very large, small resistance rates are suggested,
such as 0.02, 0.005, or even smaller, depending on the accumulative cost
values.
The values must be zero or greater. The default is 0.
Capacity
(optional)
The cost capacity for the traveler for a source.
The cost calculations continue for each source until the specified
capacity is reached.
The values must be greater than zero. The default capacity is to the edge
of the output raster.
Travel
direction (optional)
Specifies the direction of the traveler when applying horizontal and
vertical factors, the source resistance rate, and the source starting cost.
·FROM_SOURCE—The horizontal factor, vertical factor, source resistance
rate, and source starting cost will be applied beginning at the input source,
and travel out to the nonsource cells. This is the default.
·TO_SOURCE—The horizontal factor, vertical factor, source resistance rate,
and source starting cost will be applied beginning at each nonsource cell and
travel back to the input source.
If you select the String option, you can choose between from and to
options, which will be applied to all sources.
If you select the Field option, you can select the field from the source
data that determines the direction to use for each source. The field must
contain the text string FROM_SOURCE or TO_SOURCE.
Maximum
distance (optional)
The threshold that the accumulative cost values cannot exceed.
If an accumulative cost distance value exceeds this value, the output
value for the cell location will be NoData. The maximum distance is the extent
for which the accumulative cost distances are calculated.
The default distance is to the edge of the output raster.
Output
distance raster (optional)
The output path distance raster.
The output path distance raster identifies, for each cell, the least
accumulative cost distance, over a cost surface to the identified source
locations, while accounting for surface distance as well as horizontal and
vertical surface factors.
A source can be a cell, a set of cells, or one or more feature locations.
The output raster is of floating-point type.
Input
horizontal raster (optional)
A raster defining the horizontal direction at each cell.
The values on the raster must be integers ranging from 0 to 360, with 0
degrees being north, or toward the top of the screen, and increasing clockwise.
Flat areas should be given a value of -1. The values at each location will be
used in conjunction with the Horizontal factor to determine the horizontal cost
incurred when moving from a cell to its neighbors.
Horizontal
factor (optional)
Specifies the relationship between the horizontal cost factor and the
horizontal relative moving angle (HRMA).
There are several factors with modifiers from which to select that
identify a defined horizontal factor graph. Additionally, a table can be used
to create a custom graph. The graphs are used to identify the horizontal factor
used in calculating the total cost for moving into a neighboring cell.
In the descriptions below, two acronyms are used: HF stands for horizontal
factor, which defines the horizontal difficulty encountered when moving from
one cell to the next; and HRMA stands for horizontal relative moving angle,
which identifies the angle between the horizontal direction from a cell and the
moving direction.
The Horizontal factor options are as follows:
·Binary—If the HRMA is less than the cut angle, the HF is set to the value
associated with the zero factor; otherwise, it is infinity.
·Forward—Only forward movement is allowed. The HRMA must be greater than or
equal to 0 and less than 90 degrees (0 <= HRMA < 90). If the HRMA is
greater than 0 and less than 45 degrees, the HF for the cell is set to the
value associated with the zero factor. If the HRMA is greater than or equal to
45 degrees, the side value modifier value is used. The HF for any HRMA equal to
or greater than 90 degrees is set to infinity.
·Linear—The HF is a linear function of the HRMA.
·Inverse Linear—The HF is an inverse linear function of the HRMA.
·Table—A table file will be used to define the horizontal factor graph used
to determine the HFs.
Modifiers to the horizontal factors are the following:
·Zero factor—The horizontal factor to be used when the HRMA is zero. This
factor positions the y-intercept for any of the horizontal factor functions.
·Cut angle—The HRMA angle beyond which the HF will be set to infinity.
·Slope—The slope of the straight line used with the Linear and Inverse
Linear horizontal factor keywords. The slope is specified as a fraction of rise
over run (for example, 45 percent slope is 1/45, which is input as 0.02222).
·Side value—The HF when the HRMA is greater than or equal to 45 degrees and
less than 90 degrees when the Forward horizontal factor keyword is specified.
·Table name—The name of the table defining the HF.
Input
vertical raster (optional)
A raster defining the z-values for each cell location.
The values are used for calculating the slope used to identify the
vertical factor incurred when moving from one cell to another.
Vertical
factor (optional)
Specifies the relationship between the vertical cost factor and the
vertical relative moving angle (VRMA).
There are several factors with modifiers from which to select that
identify a defined vertical factor graph. Additionally, a table can be used to
create a custom graph. The graphs are used to identify the vertical factor used
in calculating the total cost for moving into a neighboring cell.
In the descriptions below, two acronyms are used: VF stands for vertical
factor, which defines the vertical difficulty encountered in moving from one
cell to the next; and VRMA stands for vertical relative moving angle, which
identifies the slope angle between the FROM or processing cell and the TO cell.
The Vertical factor options are as follows:
·Binary—If the VRMA is greater than the low-cut angle and less than the
high-cut angle, the VF is set to the value associated with the zero factor;
otherwise, it is infinity.
·Linear—The VF is a linear function of the VRMA.
·Symmetric Linear—The VF is a linear function of the VRMA in either the
negative or positive side of the VRMA, respectively, and the two linear
functions are symmetrical with respect to the VF (y) axis.
·Inverse Linear—The VF is an inverse linear function of the VRMA.
·Symmetric Inverse Linear—The VF is an inverse linear function of the VRMA
in either the negative or positive side of the VRMA, respectively, and the two
linear functions are symmetrical with respect to the VF (y) axis.
·Cos—The VF is the cosine-based function of the VRMA.
·Sec—The VF is the secant-based function of the VRMA.
·Cos-Sec—The VF is the cosine-based function of the VRMA when the VRMA is
negative and is the secant-based function of the VRMA when the VRMA is
nonnegative.
·Sec-Cos—The VF is the secant-based function of the VRMA when the VRMA is
negative and is the cosine-based function of the VRMA when the VRMA is
nonnegative.
·Table—A table file will be used to define the vertical-factor graph used
to determine the VFs.
Modifiers to the vertical keywords are the following:
·Zero factor—The vertical factor used when the VRMA is zero. This factor
positions the y-intercept of the specified function. By definition, the zero
factor is not applicable to any of the trigonometric vertical functions (COS,
SEC, COS-SEC, or SEC-COS). The y-intercept is defined by these functions.
·Low Cut angle—The VRMA angle below which the VF will be set to infinity.
·High Cut angle—The VRMA angle above which the VF will be set to infinity.
·Slope—The slope of the straight line used with the Linear and Inverse
Linear vertical-factor keywords. The slope is specified as a fraction of rise
over run (for example, 45 percent slope is 1/45, which is input as 0.02222).
·Table name—The name of the table defining the VF.
Multiplier
to apply to costs (optional)
The multiplier to apply to the cost values.
This allows for control of the mode of travel or the magnitude at a
source. The greater the multiplier, the greater the cost to move through each
cell.
The values must be greater than zero. The default is 1.
Start cost
(optional)
The starting cost from which to begin the cost calculations.
Allows for the specification of the fixed cost associated with a source.
Instead of starting at a cost of zero, the cost algorithm will begin with the
value set by Start cost.
The values must be zero or greater. The default is 0.
Accumulative
cost resistance rate (optional)
This parameter simulates the increase in the effort to overcome costs as
the accumulative cost increases. It is used to model fatigue of the traveler.
The growing accumulative cost to reach a cell is multiplied by the resistance
rate and added to the cost to move into the subsequent cell.
It is a modified version of a compound interest rate formula that is used
to calculate the apparent cost of moving through a cell. As the value of the
resistance rate increases, it increases the cost of the cells that are visited
later. The greater the resistance rate, the more additional cost is added to
reach the next cell, which is compounded for each subsequent movement. Since
the resistance rate is similar to a compound rate and generally the
accumulative cost values are very large, small resistance rates are suggested,
such as 0.02, 0.005, or even smaller, depending on the accumulative cost
values.
The values must be zero or greater. The default is 0.
Capacity
(optional)
The cost capacity for the traveler for a source.
The cost calculations continue for each source until the specified
capacity is reached.
The values must be greater than zero. The default capacity is to the edge
of the output raster.
Travel
direction (optional)
Specifies the direction of the traveler when applying horizontal and
vertical factors, the source resistance rate, and the source starting cost.
·FROM_SOURCE—The horizontal factor, vertical factor, source resistance
rate, and source starting cost will be applied beginning at the input source,
and travel out to the nonsource cells. This is the default.
·TO_SOURCE—The horizontal factor, vertical factor, source resistance rate,
and source starting cost will be applied beginning at each nonsource cell and
travel back to the input source.
If you select the String option, you can choose between from and to
options, which will be applied to all sources.
If you select the Field option, you can select the field from the source
data that determines the direction to use for each source. The field must
contain the text string FROM_SOURCE or TO_SOURCE.
Input
surface raster (optional)
A raster defining the elevation values at each cell location.
The values are used to calculate the actual surface distance covered when
passing between cells.
Maximum
distance (optional)
The threshold that the accumulative cost values cannot exceed.
If an accumulative cost distance value exceeds this value, the output
value for the cell location will be NoData. The maximum distance is the extent
for which the accumulative cost distances are calculated.
The default distance is to the edge of the output raster.
Output
distance raster (optional)
The output path distance raster.
The output path distance raster identifies, for each cell, the least
accumulative cost distance, over a cost surface to the identified source
locations, while accounting for surface distance as well as horizontal and
vertical surface factors.
A source can be a cell, a set of cells, or one or more feature locations.
The output raster is of floating-point type.
Input
horizontal raster (optional)
A raster defining the horizontal direction at each cell.
The values on the raster must be integers ranging from 0 to 360, with 0
degrees being north, or toward the top of the screen, and increasing clockwise.
Flat areas should be given a value of -1.
The values at each location will be
used in conjunction with the Horizontal factor to determine the horizontal cost
incurred when moving from a cell to its neighbors.
Horizontal
factor (optional)
Specifies the relationship between the horizontal cost factor and the
horizontal relative moving angle (HRMA).
There are several factors with modifiers from which to select that
identify a defined horizontal factor graph. Additionally, a table can be used
to create a custom graph. The graphs are used to identify the horizontal factor
used in calculating the total cost for moving into a neighboring cell.
In the descriptions below, two acronyms are used: HF stands for horizontal
factor, which defines the horizontal difficulty encountered when moving from
one cell to the next; and HRMA stands for horizontal relative moving angle, which
identifies the angle between the horizontal direction from a cell and the
moving direction.
The Horizontal factor options are as follows:
·Binary—If the HRMA is less than the cut angle, the HF is set to the value
associated with the zero factor; otherwise, it is infinity.
·Forward—Only forward movement is allowed. The HRMA must be greater than or
equal to 0 and less than 90 degrees (0 <= HRMA < 90). If the HRMA is
greater than 0 and less than 45 degrees, the HF for the cell is set to the
value associated with the zero factor. If the HRMA is greater than or equal to
45 degrees, the side value modifier value is used. The HF for any HRMA equal to
or greater than 90 degrees is set to infinity.
·Linear—The HF is a linear function of the HRMA.
·Inverse Linear—The HF is an inverse linear function of the HRMA.
·Table—A table file will be used to define the horizontal factor graph used
to determine the HFs.
Modifiers to the horizontal factors are the following:
·Zero factor—The horizontal factor to be used when the HRMA is zero. This
factor positions the y-intercept for any of the horizontal factor functions.
·Cut angle—The HRMA angle beyond which the HF will be set to infinity.
·Slope—The slope of the straight line used with the Linear and Inverse
Linear horizontal factor keywords. The slope is specified as a fraction of rise
over run (for example, 45 percent slope is 1/45, which is input as 0.02222).
·Side value—The HF when the HRMA is greater than or equal to 45 degrees and
less than 90 degrees when the Forward horizontal factor keyword is specified.
·Table name—The name of the table defining the HF.
Input
vertical raster (optional)
A raster defining the z-values for each cell location.
The values are used for calculating the slope used to identify the
vertical factor incurred when moving from one cell to another.
Vertical
factor (optional)
Specifies the relationship between the vertical cost factor and the
vertical relative moving angle (VRMA).
There are several factors with modifiers from which to select that
identify a defined vertical factor graph. Additionally, a table can be used to
create a custom graph. The graphs are used to identify the vertical factor used
in calculating the total cost for moving into a neighboring cell.
In the descriptions below, two acronyms are used: VF stands for vertical
factor, which defines the vertical difficulty encountered in moving from one
cell to the next; and VRMA stands for vertical relative moving angle, which
identifies the slope angle between the FROM or processing cell and the TO cell.
The Vertical factor options are as follows:
·Binary—If the VRMA is greater than the low-cut angle and less than the
high-cut angle, the VF is set to the value associated with the zero factor;
otherwise, it is infinity.
·Linear—The VF is a linear function of the VRMA.
·Symmetric Linear—The VF is a linear function of the VRMA in either the
negative or positive side of the VRMA, respectively, and the two linear
functions are symmetrical with respect to the VF (y) axis.
·Inverse Linear—The VF is an inverse linear function of the VRMA.
·Symmetric Inverse Linear—The VF is an inverse linear function of the VRMA
in either the negative or positive side of the VRMA, respectively, and the two
linear functions are symmetrical with respect to the VF (y) axis.
·Cos—The VF is the cosine-based function of the VRMA.
·Sec—The VF is the secant-based function of the VRMA.
·Cos-Sec—The VF is the cosine-based function of the VRMA when the VRMA is
negative and is the secant-based function of the VRMA when the VRMA is
nonnegative.
·Sec-Cos—The VF is the secant-based function of the VRMA when the VRMA is
negative and is the cosine-based function of the VRMA when the VRMA is
nonnegative.
·Table—A table file will be used to define the vertical-factor graph used
to determine the VFs.
Modifiers to the vertical keywords are the following:
·Zero factor—The vertical factor used when the VRMA is zero. This factor
positions the y-intercept of the specified function. By definition, the zero
factor is not applicable to any of the trigonometric vertical functions (COS,
SEC, COS-SEC, or SEC-COS). The y-intercept is defined by these functions.
·Low Cut angle—The VRMA angle below which the VF will be set to infinity.
·High Cut angle—The VRMA angle above which the VF will be set to infinity.
·Slope—The slope of the straight line used with the Linear and Inverse
Linear vertical-factor keywords. The slope is specified as a fraction of rise
over run (for example, 45 percent slope is 1/45, which is input as 0.02222).
·Table name—The name of the table defining the VF.
Multiplier
to apply to costs (optional)
The multiplier to apply to the cost values.
This allows for control of the mode of travel or the magnitude at a
source. The greater the multiplier, the greater the cost to move through each
cell.
The values must be greater than zero. The default is 1.
Start cost
(optional)
The starting cost from which to begin the cost calculations.
Allows for the specification of the fixed cost associated with a source.
Instead of starting at a cost of zero, the cost algorithm will begin with the
value set by Start cost.
The values must be zero or greater. The default is 0.
Accumulative
cost resistance rate (optional)
This parameter simulates the increase in the effort to overcome costs as
the accumulative cost increases. It is used to model fatigue of the traveler.
The growing accumulative cost to reach a cell is multiplied by the resistance
rate and added to the cost to move into the subsequent cell.
It is a modified version of a compound interest rate formula that is used
to calculate the apparent cost of moving through a cell. As the value of the
resistance rate increases, it increases the cost of the cells that are visited
later. The greater the resistance rate, the more additional cost is added to
reach the next cell, which is compounded for each subsequent movement. Since
the resistance rate is similar to a compound rate and generally the
accumulative cost values are very large, small resistance rates are suggested,
such as 0.02, 0.005, or even smaller, depending on the accumulative cost
values.
The values must be zero or greater. The default is 0.
Capacity
(optional)
The cost capacity for the traveler for a source.
The cost calculations continue for each source until the specified
capacity is reached.
The values must be greater than zero. The default capacity is to the edge
of the output raster.
Travel
direction (optional)
Specifies the direction of the traveler when applying horizontal and
vertical factors, the source resistance rate, and the source starting cost.
·FROM_SOURCE—The horizontal factor, vertical factor, source resistance
rate, and source starting cost will be applied beginning at the input source,
and travel out to the nonsource cells. This is the default.
·TO_SOURCE—The horizontal factor, vertical factor, source resistance rate,
and source starting cost will be applied beginning at each nonsource cell and
travel back to the input source.
If you select the String option, you can choose between from and to
options, which will be applied to all sources.
If you select the Field option, you can select the field from the source
data that determines the direction to use for each source. The field must
contain the text string FROM_SOURCE or TO_SOURCE.
Comments
Post a Comment